BELL MAKE INDUCED DRAFT / DRAUGHT COOLING TOWER SELECTION CHART

TECHNICAL SPECIFICATIONS OF AIR CONDITIONING MODELS AT DESIGNED DUTY CONDITIONS OF 97.5 'F - 90 'F - 83 i

 

 

 

 

 

 

 

 

 

 

 

 

 

TR ASSIFICATION

CELL DIMENSIONS

FAN DIA

AIR QTY.

MOTOR

RPM

OP.

INLET

OUTLET

QUICKFILL,

DRAIN,

CAP.

NO.

mm X mm X mm

mm

CFM

H.P

 

WEIGHT

SIZE

SIZE

MAKE-UP

OVERFLOW

 

 

L x B x H

 

 

 

 

(Kgs.)

 

 

SIZE

SIZE

5/7.5

ID-2004

600 x 600 x 2590

450

1675

0.5

1370

200

1.5"x2

2"

0.5"

1.5"

10

ID-2006

900 x 600 x 2590

450

2500

0.5

1370

245

1.5"x2

2"

0.5"

1.5"

15

ID-2009

900 x 900 x 2590

700

3800

1

1400

335

2" x 2

2.5"

0.5"

1.5"

20

ID-2012

1200 x 900 x 2590

700

5000

1.5

1410

440

2" x 2

2.5"

0.5"

1.5"

25

ID-2016

1200 x 1200 x 2590

700

6780

1.5

1410

565

2" x 2

2.5"

0.5"

1.5"

30

ID-2018

1350 x 1200 x 2590

700

7500

2

1415

645

2.5" x 2

3"

0.5"

1.5"

35

ID-2020

1500 x 1200 x 2590

700

8350

2

1415

710

2.5" x 2

3"

0.5"

1.5"

40

ID-2025

1500 x 1500 x 2590

700

10500

2

1415

865

3"x 2

4" 

0.5"

1.5"

50

ID-2030

1800 x 1500 x 3050

900

12600

3

945

1035

3" x 2

5"

0.5"

1.5"

60

ID-2036

1800 x 1800 x 3050

900

15100

3

945

1240

3" x 2

6"

0.5"

1.5"

70

ID-2042

1800 x 2100 x 3050

900

17600

3

945

1445

4" x 2

6"

0.75"

1.5"

80

ID-2048

2400 x 1800 x 3050

1000

20100

5

960

1635

4" x 2

6"

0.75"

1.5"

95

ID-2056

2400 x 2100 x 3050

1000

23450

5

960

1830

4" x 2

6"

0.75"

1.5"

100

ID-2060

2400 x 2250 x 3050

1000

25100

5

960

2005

4" x 2

6"

0.75"

1.5"

120

ID-2072

2400 x 2700 x 3050

1200

30150

7.5

955

2400

4" x 2

6"

0.75"

1.5"

135

ID-2080

3000 x 2400 x 3050

1200

33500

7.5

955

2645

4" x 2

4" x 2

0.75"

2.0"

150

ID-2090

3000 x 2700 x 3050

1500

37700

7.5

955

2980

5" x 2

5" x 2

0.75"

2.0"

165

ID-2100

3000 x 3000 x 3050

1800

41900

7.5

710

3145

5" x 2

5" x 2

1.5"

2.0"

175

ID-2105

3000 x 3150 x 3050

1800

44000

7.5

710

3440

5" x 2

5" x 2

1.5"

2.0"

200

ID-2120

3000 x 3600 x 3155

1800

50200

10

710

3955

5" x 2

5" x 2

1.5"

2.0"

220

ID-2132

3600 x 3300 x 3385

1200 x 2

27600 x 2

7.5 x 2

955

4215

6" x 2

6" x 2

1.5"

2.0"

240

ID-2144

3600 x 3600 x 3385

1200 x 2

30150 x 2

7.5 x 2

955

4560

6" x 2

6" x 2

1.5"

2.0"

250

ID-2150

3600 x 3750 x 3385

1200 x 2

31400 x 2

7.5 x 2

955

4845

6" x 2

6" x 2

1.5"

2.0"

280

ID-2168

3600 x 4200 x 3385

1200 x 2

35150 x 2

7.5 x 2

955

5425

6" x 2

6" x 2

1.5"

2.0"

300

ID-2180

3600 x 4500 x 3385

1500 x 2

37700 x 2

7.5 x 2

955

5810

6" x 2

6" x 2

1.5"

2.0"

325

ID-2196

4200 x 4200 x 3385

1800 x 2

41000 x 2

7.5 x 2

710

6720

6" x 2

6" x 2

1.5"

2.0"

350

ID-2210

4500 x 4200 x 3385

1800 x 2

43950 x 2

7.5 x 2

710

6885

6" x 2

6" x 2

1.5"

2.0"

375

ID-2225

4500 x 4500 x 3385

1800 x 2

47050 x 2

7.5 x 2

710

7225

8" x 2

8" x 2

1.5"

2.0"

400

ID-2240

4800 x 4500 x 3385

1800 x 2

50200 x 2

10 x 2

710

7595

8" x 2

8" x 2

1.5"

2.0"

420

ID-2252

5400 x 4200 x 3385

1900 x 2

52650 x 2

10 x 2

710

8040

8" x 2

8" x 2

1.5"

2.0"

450

ID-2270

5400 x 4500 x 3385

1900 x 2

56500 x 2

10 x 2

710

8700

8" x 2

8" x 2

1.5"

2.0"

 

NB:

1.    Considered Flow Rate - 4 USGPM/TR        # 1 CT TR = 3782 KCal / hr or 15000 BTU / hr

2.    Evaporation Loss - 0.69%, Drift Loss - 0.2%

3.    All fans are direct driven by standard make TEFC motors with IP-55 weather protection

4.    For any specific requirement, please revert to us.

5.    We reserve the right to change the specifications without any notice as the company believes in continuos                                                         

improvement and development of the product.